Belden 300% Ground Flexible VFD, 3 Conductor 16AWG (26x30) Tinned Copper, XLPE Insulation M4 Color Code+PVC Insulated Ground, Overall Beldfoil®+Tinned Copper Braid(85%) Shield w/16AWG Tinned Copper Drain, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC 1000V CSA AWM I/II A/B 600V CIC TC SUN RES DIR BUR Oil Resistant
Specifications
Specifications
Product Overview
Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 3 | 16 AWG | 26x30 | TC - Tinned Copper |
Ground Wire | 1 | 16 AWG | 26x30 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | XLPO - Crosslink Polyolefin | 0.046 in (1.2 mm) | 0.153 in (3.89 mm) | ICEA Chart M4 |
Ground Wire | PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.153 in (3.89 mm) | Green/Yellow Stripe |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Tri-Laminate (Alum+Poly+Alum) | 100% | 16 AWG (26x30) TC |
Braid | Tinned Copper (TC) | 85% | |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.534 in (13.6 mm) | Yes |
Overall Cable Diameter (Nominal) | 0.534 in (13.6 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Conductor(s) | 3.91 Ohm/1000ft | 45 pF/ft (150 pF/m) | 81 pF/ft (270 pF/m) | 41 Ohm | 55% | 18 Amps per Conductor at 30ºC |
| 4.45 Ohm/1000ft (14.6 Ohm/km) | | | | | 14.4 Amps per Conductor at 30ºC (per NEC) |
Voltage
UL Voltage Rating | Voltage Rating |
---|
600 / 1000 V (TC-ER, WTTC, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) | 1000 V (AWM I/II A/B) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | -40°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
6.4 in (160 mm) | 6.4 in (160 mm) |
Max. Pull Tension | 256 lbs (116 kg) |
---|
Bulk Cable Weight | 171 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | UL 1685 UL Loading, FT4, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, TC-ER, WTTC, UL Flexible Motor Supply Cable |
---|
AWM Compliance | AWM I/II A/B |
---|
CEC / C(UL) Compliance | CIC, TC |
---|
ICEA Compliance | S-95-658 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Other Standard Compliance(s) | P-07-KA070003-MSHA |
---|
History
Update and Revision | Revision Number: 0.570 Revision Date: 04-14-2023 |
---|