Description

Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, PP Insulation, Overall Beldfoil® Shield, PVC Outer Jacket, Flexible SUN RES OIL RES, PLTC-ER, ITC-ER, CMX-Outdoor, CM

Specifications

Specifications

Product Overview

Suitable Applicationsexposure to rodent, crush, or cut through force, harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Pair(s)118 AWG7x26TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Pair(s)PP - Polypropylene0.022 in (0.56 mm)0.088 in (2.2 mm)Blue & Orange

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%20 AWG (7x28) TC

Outer Jacket

MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.050 in (1.3 mm)0.280 in (7.11 mm)
Table NotesJacket OD +/- 0.010
Overall Cable Diameter (Nominal)0.280 in (7.11 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Capacitance UnbalanceNom. Capacitance Cond-to-ShieldNom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Pair(s)7.2 Ohm/1000ft1.2 pF/ft (3.9 pF/m)45 pF/ft100 Ohm66%5.2 Amps per Conductor at 25ºC
Nom. Outer Shield DCR8.5 Ohm/1000ft (28 Ohm/km)

High Frequency (Nominal/Typical)

ElementFrequency [MHz]Nom. Insertion Loss (Attenuation)
Pair(s)0.0390.08 dB/100ft

High Frequency

Frequency [MHz]Max. Insertion Loss (Attenuation)Max./Min. Input Impedance (unFitted) [Ohm]
0.0310.091 dB/100ft100

Voltage

UL Voltage Rating
300 V (CM, PLTC-ER), 150 V (ITC-ER)

Mechanical Characteristics

Temperature

UL TemperatureOperating
105°C-40°C to +105°C

Bend Radius

Stationary Min.Installation Min.
6.5 in (170 mm)2.80 in (71.1 mm)
Max. Pull Tension60 lbs (27 kg)
Bulk Cable Weight44 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Oil Resistance, Oil Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, FT4, IEEE 1202, IEC 60332-1-2
CPR ComplianceCPR Euroclass: Eca; CPR UKCA Class: Eca
NEC / UL ComplianceArticle 725, Article 727, Article 800, CMG, ITC, PLTC, TC
CEC / C(UL) ComplianceCMG
ISO/IEC ComplianceIEC 61158-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
Other Standard Compliance(s)ISA/SP-50 Type A

Product Notes

NotesFieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Jacket diameter tolerance: +/- .010

History

Update and RevisionRevision Number: 0.530 Revision Date: 04-14-2023
View AllClose

Additional Information

Variant_Options:
Item #|Color|Putup Type|Length|UPC
Variant_Options 3076F 0061000:
3076F 0061000|Blue, Light|Reel|1,000 ft|612825140269
Variant_Options 3076F 00310000:
3076F 00310000|Orange|||612825140214
Variant_Options 3076F 003250:
3076F 003250|Orange|Reel|250 ft|612825140221
Variant_Options 3076F 003500:
3076F 003500|Orange|Reel|500 ft|612825140245
Variant_Options 3076F 0031000:
3076F 0031000|Orange|Reel|1,000 ft|612825140207
Variant_Options 3076F 0032500:
3076F 0032500|Orange|Reel|2,500 ft|612825140238
Variant_Options 3076F 0035000:
3076F 0035000|Orange|Reel|5,000 ft|612825140252
View AllClose