Fire Alarm Cable, Plenum-FPLP, 2-16 AWG solid bare copper conductors with Flamarrest® insulation, overall Beldfoil® shield, Flamarrest® jacket with ripcord
Specifications
Specifications
Product Overview
Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 2 | 16 AWG | Solid | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.010 in (0.25 mm) | 0.071 in (1.8 mm) | Black, Red |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (Solid) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.178 in (4.52 mm) | Yes |
Overall Cable Diameter (Nominal) | 0.178 in (4.52 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|
Conductor(s) | 3.85 Ohm/1000ft | 77 pF/ft (250 pF/m) | 139 pF/ft (456 pF/m) | 14.4 Amps per conductor @ 25°C |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | 0°C to +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.67 in (67.8 mm) | 2.67 in (67.8 mm) |
Max. Pull Tension | 68 lbs (31 kg) |
---|
Bulk Cable Weight | 26 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor - Plenum, Indoor |
---|
Flammability / Reaction to Fire | NFPA 262, UL 910 (Plenum), IEC 60332-1-2 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 760, FPLP |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Other Standard Compliance(s) | California State Fire Marshall |
---|
Non-Plenum Number | 5220FL |
---|
History
Update and Revision | Revision Number: 0.462 Revision Date: 04-03-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets