Suitable Applications | fire alarms; indoor applications; low voltage analog signals (4-20ma, 0-10v, ...); low voltage control (24v, …) |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 2 | 14 | Solid | BC - Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
PVC - Polyvinyl Chloride | 0.022 in (0.56 mm) | 0.20 in (5.1 mm) | Black, Red |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 16 AWG (19x29) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.042 in (1.1 mm) | 0.306 in (7.77 mm) |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|
2.62 Ohm/1000ft | 55 pF/ft (180 pF/m) | 105 pF/ft (344 pF/m) | 18 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
105°C | -40°C To +105°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
4.59 in (117 mm) | 4.59 in (117 mm) |
Max. Pull Tension | 124 lbs (56.2 kg) |
---|
Bulk Cable Weight | 60 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor |
---|
Flammability / Reaction to Fire | UL1666 Riser, FT4, IEC 60332-1-2 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 760, FPLR |
---|
AWM Compliance | AWM 2464 |
---|
CEC / C(UL) Compliance | FAS105 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Other Standard Compliance(s) | California State Fire Marshall |
---|
Product Notes
Notes | This cable passes the UL 1685 70,000 BTU Flame Test (comparable to the IEEE 383 Flame Test) and is listed by the California State Fire Marshall. Component Recognized UL 2464, 300V 80░C. |
---|
History
Update and Revision | Revision Number: 0.511 Revision Date: 01-20-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets