Belden

GIBTD08 - Indoor tight buffered breakout cable LSZH jacket 8f MM OM3. CPR Dca.

(No reviews yet) Write a Review
SKU:
GIBTD08
Shipping:
Calculated at Checkout
$0.00

Description

Indoor tight buffered breakout cable with Low Smoke Zero Halogen outer jacket. 8 fibers MM OM3. CPR Euroclass Dca.

Specifications

Specifications

Product Overview

Environmental SpaceIndoor - Euroclass Dca
Suitable ApplicationsFor indoor use in structured (premises) wiring systems: building backbone (riser) and/or horizontal cabling (Fibre To The Desk). Support all computer network applications such as FDDI, Gigabit Ethernet and ATM. Easy to install in ducts and tunnels.

Construction

Fiber Cable Construction

Fiber TypeFiber Count
OM38
Fiber Color CodingTIA coding (Gxxxxxx.T): Blue

Buffer Specification

Fiber TypeBuffer ConstructionBuffer MaterialBuffer Diameter
OM3TightLSZH - Low Smoke Zero Halogen (Flame Retardant)0.9 mm
Central Strength MemberLSZH Filler
Cable Core Water TightNo
Bulk Cable Weight81 kg/km

SubUnit Specifications

Number of Active Subunits8
Number of Subunit Positions8
Fibers Per Subunit1

Jacket Specifications

Number of JacketsSingle Jacket
Type of ArmorNon-Armored

Outer Jacket Specifications

Outer Jacket

MaterialNominal DiameterRipcord
LSZH - Low Smoke Zero Halogen (Flame Retardant)9.4 mmYes
Table NotesStandard color: Orange. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green

Optical Characteristics

Max. Attenuation at 1300 nm0.9 dB/km
Max. Attenuation at 850 nm2.9 dB/km

Mechanical Characteristics

Mechanical Tests

DescriptionTested StandardRequirement/ValueAccording to Family Specification
Cable Min. Bend Radius Installation (Short Term)IEC 60794-1-21-E6188 mmIEC 60794-2-20
Cable Min. Bend Radius Operation (Long Term)IEC 60794-1-21-E1194 mmIEC 60794-2-20
Cable Max. Tensile Strength Installation (Short Term)IEC 60794-1-21-E1770 N (173 lbf)
Cable Max. Crush Resistance Installation (Short Term)IEC 60794-1-21-E35 kN/mIEC 60794-2-20
Cable Max. Crush Resistance Operation (Long Term)IEC 60794-1-21-E33 kN/mIEC 60794-2-20

Temperature Range

Operating Temperature Range-5 °C to +55 °C
Installation Temperature Range-5 °C to +50 °C
Storage Temperature Range-5 °C to +55 °C

Standards

UL Rating/Flame TestNon-UL Rated
IEC FlammabilityIEC 60332-1-2
Reaction to Fire - Bundle Flame TestIEC 60332-3-24
IEC 60754-1 - Halogen AmountZero
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity10 µS/mm
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH4.3
IEC 61034-2 - Smoke Density Min. Transmittance60%
CPR EuroclassDca-s1,d1,a1
REACHCompliant
ISO/IEC ComplianceIEC 60794
UV/ Sunlight ProtectionYes

History

Update and RevisionRevision Number: 0.71 Revision Date: 01-20-2023
View AllClose