Description

Universal (Indoor/Outdoor) tight buffered breakout cable with Low Smoke Zero Halogen outer jacket. 6 fibers MM OM4.

Specifications

Specifications

Product Overview

Environmental SpaceIndoor/Outdoor
Suitable ApplicationsFor outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Support all computer network applications such as FDDI, Gigabit Ethernet and ATM.

Construction

Fiber Cable Construction

Fiber TypeFiber CountSubunit Color
OM46TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White
Fiber Color CodingTIA coding (Gxxxxxx.T): Blue

Buffer Specification

Fiber TypeBuffer ConstructionBuffer MaterialBuffer Diameter
OM4TightLSZH - Low Smoke Zero Halogen (Flame Retardant)0.9 mm
Central Strength MemberGRP
Cable Core Water TightYes
Cable Core WaterblockingWaterblock Tape
Bulk Cable Weight59 kg/km

SubUnit Specifications

Number of Active Subunits6
Number of Subunit Positions6
Fibers Per Subunit1

Jacket Specifications

Number of JacketsSingle Jacket
Type of ArmorNon-Armored

Outer Jacket Specifications

Outer Jacket

MaterialNominal DiameterRipcord
LSZH - Low Smoke Zero Halogen (Flame Retardant)8.0 mmYes
Table NotesStandard color: Erika Violet. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green

Optical Characteristics

Max. Attenuation at 1300 nm0.9 dB/km
Max. Attenuation at 850 nm2.9 dB/km

Mechanical Characteristics

Mechanical Tests

DescriptionTested StandardRequirement/ValueAccording to Family Specification
Cable Min. Bend Radius Installation (Short Term)IEC 60794-1-21-E6160 mmIEC 60794-2-20
Cable Min. Bend Radius Operation (Long Term)IEC 60794-1-21-E1180 mmIEC 60794-2-20
Cable Max. Tensile Strength Installation (Short Term)590 N (133 lbf)IEC 60794-2-20
Cable Max. Tensile Strength Operation (Long Term)IEC 60794-1-21-E1
Cable Max. Crush Resistance Installation (Short Term)IEC 60794-1-21-E35 kN/mIEC 60794-2-20
Cable Max. Crush Resistance Operation (Long Term)IEC 60794-1-21-E33 kN/mIEC 60794-2-20

Temperature Range

Operating Temperature Range-30 °C to +70 °C
Installation Temperature Range-5 °C to +50 °C
Storage Temperature Range-30 °C to +70 °C

Standards

UL Rating/Flame TestNon-UL Rated
IEC FlammabilityIEC 60332-1-2
IEC 60754-1 - Halogen AmountZero
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity10 µS/mm
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH4.3
IEC 61034-2 - Smoke Density Min. Transmittance60%
REACHCompliant
ISO/IEC ComplianceIEC 60794
UV/ Sunlight ProtectionYes

History

Update and RevisionRevision Number: 0.42 Revision Date: 03-16-2023